A nozzle off a 600mm propane header had experienced severe corrosion under insulation (CUI) and a leak had developed. While the line was live it would ice up, so this case required a short shut down in which to apply the Technowrap™ solution. To achieve a rapid cure, heat tapes were used to control the cure speed. The geometry and corrosion required a defect design of full circumferential wall loss over a 300mm length.
The line had the following specifications:
Structure | 600mm header with nozzle |
Surface Preparation | Sa 2.5 |
Class Approval | N/A |
Design Pressure | 1,740 kPa |
Design Temperature | -42 0C to 650C |
Application Temperature | 100C |
Design Life | 5 years |
Wrap Length | 550 mm |
Pipe Diameter | 25 mm |
Geometry | Wrap over valve, nozzle and header line |
Corrosion Type | External |
Defect Details | 300mm circumferential slot (through-wall) |